Lo-Trim II measurements

Single Element Lo-Trim II Hot Water Ratings BTU per hour per linear foot of active (finned) length (with damper).

AVERAGE HOT WATER TEMPERATURE °F – BTU/Hr./Linear Ft.
    140° 150° 160° 170° 180° 190° 200° 210° 220°
1/2" 4 GPM 330 390 450 520 590 670 740 820 900
1 GPM 310 370 430 490 560 630 700 780 850
3/4" 4 GPM 320 380 440 510 570 630 710 770 840
1 GPM 300 360 420 480 540 600 670 730 790

The use of I=B=R Rating @ 4GPM is limited to installations where flow rate is known to be equal to or greater than 4 GPM. If flow rate is unknown, use 1 GPM rating.

I=B=R Ratings include 15% addition to water heat capacity.

Hot water ratings shown are at the STANDARD WATER FLOW RATE of 500 lb/hr (1GPM) and 2,000 lbs/hr (4GPM) with 65º entering air temperature.

Friction loss through Argo Baseboard unit at 1 GPM (500 lbs/hr) is 47 MIL-INCHES per foot and at 4 GPM (2000 lbs/hr) is 525 MIL-INCHES PER FOOT.

Rating base on active length. Difference between active and total length is 3".

Aluminum fins are 2 1/8" x 2 1/8" x .008" thick, spaced 51 per foot (unpainted).

All hot water ratings shown in this table determined in conformance with I=B=R Baseboard Rating committee.

I=B=R Approved Ratings